ICC710-HD1-C1 Technical Specification
project
explain
Outdoor cabinet
Temperature control:
Equipment compartment: heat exchange, heat dissipation 150W/K (when the temperature is between 40-45 ℃ and solar radiation, the heat exchange heat dissipation decreases to 110W/K)
Battery room: direct ventilation
Overall dimensions (height × wide × Depth: 1925mm × 900mm × 1120mm
Base size (height × wide × Depth: 150mm × 900mm × 950mm
Weight: 300kg
Installation method: floor mounted
Maintenance method: front-end maintenance
Wiring method: bottom-up
working temperature
-10 ℃ to+40 ℃ (when using TCB-C batteries, temperature range: -10 ℃ to+45 ℃)
Explanation:
When the temperature is below -5 ℃, a low battery temperature alarm may occur, affecting the backup performance of the battery.
Transportation temperature
–40℃~+70℃
Storage temperature
–40℃~+70℃
Working humidity
5% relative humidity to 95% relative humidity (non condensing)
Altitude requirements
0m~4000m (in a high temperature derating environment of 2000m~4000m, for every 200m increase, the operating temperature decreases by 1 ℃)
noise level
Meet the requirements of GR487, with noise pressure ≤ 65dBA@1.5m (When the ambient temperature is 45 ℃)
Protection level and working environment
IP55, Class C environment
Other requirements
No conductive dust and corrosive gases, no explosion hazard
Dust levels, corrosive substances, harmful organisms, molds, and other indicators should meet the requirements of ETSI EN 300 019-1-4 (V2.2.1) level 4.1
Internal structure of 8 ICC710-HD1-C1 (front)
(1) RTN+copper bar
(2) Heat exchange
(3) Fan box
(4) Terminal block
(5) DCDU-400AN2 type
(6) -48V copper bar
(7) Battery installation space
Figure 3-9 Internal Structure of ICC710-HD1-C1 (Back)
(1) Grounding rod